Mounting on 100mm
Bus bar systems
Mounting on 185mm
Bus bar systems with adapter top/bottom cable terminal
Item | Item-No. | kg/pc. | Packaging |
NH 00 MSL with clamp straps 4-70mm2 | 14 8055 | 1,12 | 1 |
NH 00 MSL with V-connection | 14 8056 | 1,12 | 1 |
V clamps (1x) | 14 2908 | 0,04 | 1 |
Claw strap (set) for direkt assemby | 14 8063 | 0,1 | 1 |
Single adapter for mounting on 185mm SS-System | 14 8066 | 0,45 | 1 |
Twin adapter for mounting on 185mm SS-System | 14 8067 | 0,85 | 1 |
Single adapter for mounting on 185mm / claw strap | 14 8076 | 0,56 | 1 |
Twin adapter for mounting on 185mm / claw cramp | 14 8077 | 0,45 | 1 |
cover shield, set=2 pieces | 14 8061 | 0,45 | 1 |
Single adapter for current transformer | 14 0117 | 0,34 | 1 |
Twin adapter for current transformer | 14 0119 | 0,58 | 1 |
Current transformer for adapter 100 A, single-phase | 14 0121 | 0,51 | 1 |
Current transformer for adapter 100 A, triple-phase | 14 0122 | 0,78 | 1 |
Current transformer for adapter 150 A, single-phase | 14 0123 | 0,52 | 1 |
Current transformer for adapter 150 A, triple-phase | 14 0124 | 0,81 | 1 |
Primary tube for adapter as spacer (set = 3x) | 14 0125 | 0,37 | 1 |
NH 00 MSL | |||
No. of poles | 3 | ||
Conventional free air thermal current links NH lth | 160A | ||
Rated operational voltage Ue | 690V AC | ||
Rated insulation voltage Ui | 1000V | ||
Rated impulse withstand voltage Uimp | 8kV | ||
Conditional short circuit making capacity mit NH | |||
AC 400V | 80kA | ||
AC 500V | 80kA | ||
AC 690V | 50kA | ||
Utilization category | Rated operational voltage | current Ie | |
AC 23B | 400V | Ie= | 160A |
AC 22B | 500V | Ie= | 160A |
AC 21B | 690V | Ie= | 100A |
Degree of protection | IP 30 | ||
max. permissible power dissipation of solid links Pn | 12W |